Wire material requirements simple access control installation
Details of the problem:

Prepare to install a set of simple access control, want to know the wiring requirements, such as signal line, lock line, switch line specification and limiting length?

Expert answer:

Hello, thanks for using our products.

The AC220V power cord is recommended to use 3*1.0 square mm (or above) wire.

The cable is recommended to use 2*1.0 square mm (or above) wire, and the longest walking distance is not more than 50 meters.

The RS485 communication line recommends the use of 2* 0.5mm (or above) wire, which is recommended to use a shielded wire, with the longest walking distance not exceeding 1200 meters.

TCP/IP communication lines is recommended to use the standard line, the longest walking distance is not more than 100 meters.

The card reader line recommends using 8*0.5 square mm (or above) wire, the longest walking distance is not more than 80 meters.

Door magnetic or exit switch lines suggest using 2*0.5 square mm (or above) wire, the longest running distance is not more than 100 meters.